Applications
• Application in wind, Solar, Wind&Solar hybrid power generation station.
• Application in household wind&solar hybrid power generation system.
• Power supply for those unmanned regions like the coastal islands, remote mountainous regions and border posts.
Features
• Can be applied in wind, solar, wind&solar hybrid power generation system.
• Simple structure, complete function
• Low no-load loss by using industrial frequency transformer
• RS232/RS485/GPRS optional (Those with GPRS can also be monitored through App.)
• CE certification
Technical Parameters |
|||||||
Model |
WI100-96 |
WI100-120 |
WI100-240 |
WI200-240 |
WI300-240 |
||
DC Input Parameters |
|||||||
Rated battery voltage |
96Vdc |
120Vdc |
240Vdc |
240Vdc |
240Vdc |
||
Input overvoltage point |
136Vdc |
170Vdc |
340Vdc |
340Vdc |
340Vdc |
||
Input overvoltage recovery point |
132Vdc |
165Vdc |
330Vdc |
330Vdc |
330Vdc |
||
Input undervoltage point |
86.4 Vdc |
108Vdc |
216Vdc |
216Vdc |
216Vdc |
||
Input undervoltage recovery point |
96Vdc |
120Vdc |
240Vdc |
240Vdc |
240Vdc |
||
AC Output Parameters |
|||||||
Output phase number |
Single phase |
||||||
Rated output power |
10kW |
10kW |
10kW |
20kW |
30kW |
||
Rated output voltage |
110/120/220/230/240Vac |
||||||
Rated output frequency |
50/60±0.5HZ |
||||||
THDi |
<5% |
||||||
Efficiency |
|
||||||
Max. conversion efficiency |
≥85% |
||||||
Protection Functions |
|
||||||
DC input overvoltage protection |
YES |
||||||
DC reversed connection protection |
YES |
||||||
AC output overload protection |
YES |
||||||
AC short circuit protection |
YES |
||||||
Surge protection |
YES |
||||||
Over-temperature protection |
YES |
||||||
General Parameters |
|
||||||
Display mode |
LCD |
||||||
Display information |
Battery voltage, inverter voltage, inverter current, inverter power, and working status of battery overvoltage/undervoltage and AC output overload/short circuit. |
||||||
Monitoring mode(optional) |
RS232/RS485/GPRS |
||||||
Monitoring Contents |
Real-time display: Battery voltage, inverter voltage, inverter current, inverter power, and working status of battery overvoltage/.undervoltage and AC output overload/short circuit. |
||||||
Parameter setting: overvoltage point, overvoltage recovery point, undervoltage point, and undervoltage recovery point. |
|||||||
Isolation mode |
Industrial frequency isolation |
||||||
No-load current |
≤1.5A |
≤1.5A |
≤1.0A |
≤0.9A |
≤1.5A |
||
Environment temperature |
-20℃~+40℃ |
||||||
Humidity |
5%~95%, No condensing |
||||||
Noise |
<60dB |
||||||
Cooling mode |
Forced air cooling |
||||||
Cover protection class |
IP20 |
||||||
Product dimension(W*H*D) |
500×725×500mm |
600×1180×600mm |
|||||
Product net weight |
75kg |
200kg |
260kg |
||||
Note: Part of parameters can be adjusted according to customer’s specific demand. |
Application